Control Freak
LIDA-D – DALI Relay Controller
Description
LIDA-D – DALI relay controller
Overview
The LIDA-D is expertly designed to offer versatile control of relays for switched loads such as contactor control, pumps, non-dim lighting and more. This device distinguishes itself by its capability to manage either one or two ceiling fans, or alternatively, between one and four relays/contactors.
Installation of the LIDA-D necessitates professional handling by qualified electricians as it is capable of switching mains voltages. The device operates on a DC input, with a flexible power supply requirement ranging from 8 to 40VDC and a minimum current of 50mA. For scenarios where the LIDA-D is directly powering loads (of up to 57W @ 240VAC), a more robust supply of 1.2A for 240mA loads is recommended, ensuring reliable and uninterrupted operation.
Features
- Versatile Control Options: Engineered for flexibility, the LIDA-D allows switched loads to be controlled by a DALI network
- Flexibility: Easy way to add mechanical ventilation, non-dim lighting to a DALI line … just about anything that can be switched. Direct loads up to 57W @240VAC, or interpose relays for larger loads. DC can also be switched.
Downloads
- Lida-D
- Lida-D User Manual
- Warranty
Specification
| Description | Details | 
|---|---|
| Control | Data Protocol: Standard DALI | 
| Modes: Fan or relay control, 1-4 DALI devices, n/o or n/c outputs, fan kick start enable/disable | |
| Physical | Size (mm): LIDA-D 105 x 71 x 59 (l/h)x(w)x(d) | 
| LIDA-F 205 x 205 x 76 (l/h)x(w)x(d) | |
| Weight: 0.12kg unpacked | |
| 1kg unpacked | |
| Mounting: Suits standard 35mm din rail | |
| Shelf or wall | |
| Power | DC Input: 9-36VDC | 
| Consumption: At 24V DC IN = 8.6mA (idle), 15.5mA (max). DALI current draw is just 1.6mA. | |
| AC Input: Universal 90-264VAC, 50-60Hz | |
| Protection | DC: Transient protection. Over-voltage protection. Reverse polarity immunity. Back EMF suppression. Accidental 240VAC immunity on DALI. | 
| AC: Transient protection between input and output of up to 2000V for up to 10milliseconds | |
| Connections | External trigger LIDA-D ONLY: Trigger 1 to LIDA gound via switch or relay eg manual override. Latching NO switch when closed will force all channels on and ignore all DALI commands until open. Optional bespoke functionality | 
| Inputs and outputs: LIDA-D Screw terminals in removable plug and socket array for easy wiring | |
| LIDA-F Screw terminals with wiring access slot, labeled terminals, location for easy mounting of capacitors | |
| Status LEDs | Mimic leds: One status led per channel. On = channel on. LIDA-D enclosure also has DC in status led mimic. | 
| Other | Temperature: Design Ta =65 deg C (no oscillator drift), 80 deg C max | 




 eDIDIO Series 10 – 4 Pole (1 Output Line)
 eDIDIO Series 10 – 4 Pole (1 Output Line) UBi Power V2
 UBi Power V2 ADDICT V3 – Full Kit
 ADDICT V3 – Full Kit WhatsApp Chat
			                WhatsApp Chat